Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-1024-05768
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/14/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/14/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1024-05768 (1432 E MOSSMAN RD Unit:UNIT 27 TUCSON, AZ 85706) 2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. 1. Show the connection and length from the meter to ALL attached appliances, G2401.1, R301.1: Include pipe size, type and length. 2. The ¾” pipe going from the meter to the range is undersized for the given length and appliance demand. A minimum of 1" pipe size is required. 3. The 1/2” pipe going from the main gas line to the furnace appears to be undersized for the given length and appliance demand. A minimum of 3/4" pipe is required. Here are the Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions: building_official@tucsonaz.go |
||
10/14/2024 | PDSD Application Completeness | REVIEW COMPLETED |