Permit Number: TC-RES-1024-05768
Parcel: 140250950

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1024-05768
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
10/04/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT TC-RES-1024-05768 (1432 E MOSSMAN RD Unit 27 TUCSON, AZ 85706)

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC).

1. Provide total demand from all appliances, G2413.2.
Provide a gas piping plan showing the connection from the meter to ALL attached appliances. Include pipe size, type, and length. Show connection, lengths, and sizes, from gas meter to all gas appliances. Modifications to the gas system requires the submission of a gas pipeline template (or equivalent), G2401.1, G2413.1, R301.1.
Gas Lines- Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes.
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/gas_handout_2018_irc_2019.2.4.pdf
2. The Owner/builder waver must be filled out and signed by the owner of the property and that person much be listed on the permit as the owner/builder.
building_official@tucsonaz.gov
10/04/2024 PDSD Application Completeness REVIEW COMPLETED