Permit Number: TC-RES-1024-05766
Parcel: 140250950

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-1024-05766
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
10/14/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1024-05766 (1432 E MOSSMAN RD Unit:UNIT 25 TUCSON, AZ 85706)

2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

1. Show the connection and length from the meter to ALL attached appliances, G2401.1, R301.1: Include pipe size, type (Black Iron, Poly) and length. The length and pipe size from the main gas line to the stove was not provided.
2. The ¾” pipe going from the meter to the stove is undersized for the given length and appliance demand. A minimum of 1" pipe size is required.
3. The 1/2” pipe going from the main gas line to the furnace appears to be undersized for the given length and appliance demand. A minimum of 3/4" pipe is required.

Here are the Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf

For questions: building_official@tucsonaz.gov.
10/14/2024 PDSD Application Completeness REVIEW COMPLETED