Permit Number: TC-RES-1024-05738
Parcel: 128072150

Review Status: In Review

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1024-05738
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
N/A Bldg Permits - Post Review PENDING ASSIGNMENT
N/A Site Engineering PENDING ASSIGNMENT
N/A Site Zoning PENDING ASSIGNMENT
10/17/2024 Residential Building REQUIRES RESUBMIT TC-RES-1024-05738
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require may require further changes for providing minimum code compliance of construction performed with a permit.

Note the 2018 IRC reference on the plans.

Provide a response letter on separate file with the updated construction plan set.

Provide a clear and concise construction plan set. Sample drawings are available for understanding details. Sample plans at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

PLANS:

1. Clarify the alterations performed at the Flex Room, R106.1.

SECTIONS - DETAILS:

1. Provide a wall detail showing a 6” minimum separation of exterior siding or sheathing above finished grade, R317.1 item 5. Also, show the weep screed with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1. This may require a design with concrete stems.

MECHANICAL PLANS:

1. Show the HVAC supply vent size for the addition, M1401.3 & M1601.1.

ELECTRICAL PLANS:

1. Show receptacle outlets with no wall point (exclude door openings) more than 6’ from a receptacle outlet at existing and proposed walls, E3901.2.
2. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. Add a note to plans.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
----------------------
10/08/2024 PDSD Application Completeness REVIEW COMPLETED