Permit Number: TC-RES-1024-05691
Parcel: 10821008D

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1024-05691
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2024 Site Engineering NOT REQUIRED
11/07/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/14/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1024-05691 (4340 N MAINARD DR TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. For wind uplift use 115 mph in 3sec gust, Table R301.2(1). https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf
2. Provide the engineer’s calculations reports for the foundation design and PV structural design, R106.5.
3. Provide a Grounding Electrode System at the detached structure per NEC 690.47.
4. Show the Grounding Conductor’s connection at the modules, mounting and metal support structure.
5. Show grounding details for the mounting equipment and metal support frame, NEC690.43.

6. Per the foundation side view, this project requires the following special inspections:
A: Helical/drilled piers foundation.
7. Provide a Special Inspection Certificate, with Parts A and B completed. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf

Fire separation:
1. Show that the Gravel Driveway is a registered access easement or provide 3-foot fire separation from the property line.
2. Any structure placed within the 3-foot fire separation distance, from the neighboring property line, requires not less than one-hour fire-resistive construction for reducing fire spread across the line, R302.1(City of Tucson Amended). Fire rated materials are found in IBC Table 721.1(2), Items 15-1.1 to 16-1.3.
3. Roof projections extending into the 3-foot fire separation distance require not less than one-hour fire-resistive construction on the underside, R302.1 (City of Tucson Amended). The fire protected overhang may not extend closer than 24” from the line used to determine the fire separation distance.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
11/07/2024 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Fernando Garcia
Planning & Development Services Department – Zoning Review Section

PROJECT:
TC-RES-1024-05691 – Residential Building
4340 N Mainard Dr, Tucson, AZ 85719
Plan Review (1st Review)

TRANSMITTAL DATE: November 7, 2024

This site is zoned MH-1 (UDC Section 4.7.10). A detached single-family dwelling is a permitted use in the MH-1 zone. Solar energy collectors are permitted as an accessory use.

1. (Comment) Provide setback distances for the new canopy on the site plan. Setback should be measured from the outside face of the canopy post to the nearest property lines. Per the site plan, the canopy appears to be detached. It also appears to be within the required 6’ or 2/3 of wall height (whichever is greater) setback distance.

Per UDC Section 6.6.2., “An accessory structure , except for an accessory dwelling unit , that exceeds the allowable height of a wall within a perimeter yard and is detached from a principal structure shall comply with the perimeter yard width standards of the principal structure , except that the accessory structure may be built to a parcel line with the consent of the adjoining or, when separated by an alley, adjacent property owner(s)”

On resubmittal, provide a copy of the signed neighbor waiver language on the site plan. The waiver language follows:

“My name is ______ and I am the owner of the property located at ______. I have reviewed the site plan and I have no objection to the structure being located or construct __ feet from the property line as depicted on the site plan.

Signature: ________

Date: _________”

If the neighbor refuses to sign, then a Design Development Option (DDO) would be required to be approved to allow the reduced setback for the canopy. For more information about the DDO process, including application, reach out to Mark Castro at mark.castro@tucsonaz.gov or 520-837-4979 for more information.

2. (Comment) Per UDC 6.6.3.D, a detached accessory structure – such as this canopy – is only permitted to be a height of 12’ as measured from design grade. The site plan shows 12’ 11” ½.

A variance granted by the Board of Adjustment would be required for a height above 12’. You can also reach out to Mark Castro at the contact information provided in comment 1 above about the Board of Adjustment process and requirements.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Resubmittal of revised plans and comment response letter indicating how comments were addressed.

If you have any questions about this transmittal, please contact Fernando L. Garcia at fernando.garcia2@tucsonaz.gov. For faster review, provide notice to this reviewer by email on resubmittal.
10/02/2024 PDSD Application Completeness Express REVIEW COMPLETED