10/03/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1024-05678 (2222 E TOWNER ST TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide an updated Plan and a written response letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response letter addressing the comments below maybe be delayed until the response letter is received.

1. You're gas template/drawing is missing the pipe size for the main line from meter to all appliances must be a minimum of 1 1/4'', see drawing for markups. In addition, the pipe size for fireplace and furnace is undersized and must be a minimum of 1'', see drawing for markups. For questions: Building_Official@tucsonaz.gov