Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-1024-05678
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/03/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
10/03/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1024-05678 (2222 E TOWNER ST TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide an updated Plan and a written response letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response letter addressing the comments below maybe be delayed until the response letter is received. 1. You're gas template/drawing is missing the pipe size for the main line from meter to all appliances must be a minimum of 1 1/4'', see drawing for markups. In addition, the pipe size for fireplace and furnace is undersized and must be a minimum of 1'', see drawing for markups. For questions: Building_Official@tucsonaz.gov |
||