Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-1023-09173
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/01/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/01/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1023-09173 (7315 E SYLVANE DR TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. The ½” pipe to the Furnace is undersized for the given length and demand. Size the pipe based on the length from the meter to the furnace and max total demand of the furnace using Table G2413.4(1) (Metallic Pipe), Note: The length is measured from the meter to the furthest furnace for sizing the branch line to the furnace, G2413.4.1. ¾” BIP is minimum required size for this branch. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 11/01/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |