Permit Number: TC-RES-1023-09158
Parcel: 140062630

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1023-09158
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2023 Site Engineering NOT REQUIRED
11/14/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/14/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1023-09158 (5525 S OLYMPIA SV TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Provide an electrical riser diagram, 2017 NEC 230.9. Notate the grounding and bonding method, 2017 NEC 250.20(B), 250.24, 250.30(A)(4). Metallic gas lines must be bonded and not be used as the primary grounding method, 2017 NEC 250.50, 250.52(B)(1).

2. Show the mast height on the electrical riser diagram, NEC 230.24.
a. Providing 8’ clearance above the roof or relocate the service entrance to a code compliant location, 2017 NEC 230.24(A).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/31/2023 PDSD Application Completeness Express REVIEW COMPLETED