Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-1023-09077
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2023 | Site Engineering | NOT REQUIRED | |||
| 11/13/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/13/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1023-09077 (5210 E BAKER ST TUCSON, AZ 85711) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Provide conductor sized according to E3705.5.3 Small conductors: Sheet PV-4 and PV-5 shows a #10 AWG conductor, Raceway # 6-8, connected to a 35A breaker. Per Table E3705.5.3 [NEC240.4(D)] max OCPD for a #10 AWG conductor is 30A. 2. OCPD for copper conductor may not exceed 30A for #10 rating required by NEC 240.4(D)(small conductors), For larger than #10AWG, see NEC Table 310.15(B)(16). 3. Updated plans shall include the EOR seal. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||