Permit Number: TC-RES-1023-09073
Parcel: 113070990

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1023-09073
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2023 Site Engineering NOT REQUIRED
11/14/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/14/2023 Residential Building REQUIRES RESUBMIT TC-RES-1023-09073
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

FLOOR PLAN:

1. Individual dwelling units require separation by a fire rated wall from floor to bottom of roof sheathing without openings, R302.4. Remove the door opening between dwelling units (with kitchens) and add one-hour rating of the separating wall or provide a plan showing the removal of the existing kitchen, R301.1.

STRUCTURAL PLANS:

1. Provide complete structural (roof framing) plan for the guest quarters addition showing compliance with the IRC or provide an Arizona structural engineer plan set showing performance compliance, R301.1. 2x6 rafters are undersized.

2. The proposed Patio Cover may be sited within the 3’ fire separation distance from a property line. Show compliance with R302.1 (City of Tucson Amended) by providing a wall with one-hour rated materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3, R106.1 or remove any structure closer than 3 feet to the property line.

SECTIONS - DETAILS:

1. Show a minimum ½” diameter anchor bolt with 7” embedment into concrete or masonry, R403.1.6. Update detail #4/A1 for showing the minimum requirement for both load bearing and non-bearing walls.
2. Attic space requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

PLUMBING PLANS:

1. Show an individual accessible water supply shut off for the proposed dwelling or remove the existing kitchen, P2903.9.1.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Show the airflow rate setting or remove the existing kitchen. A one-bedroom dwelling under1501 SF requires a 30 CFM continuous setting.

ELECTRICAL PLANS:

1. Provide an engineer’s design and seal for any service greater than 400 AMPS.
2. Provide a Riser Diagram showing sub panel feeder sizes, NEC 225.30, E3403, Table E3704.2(1).
3. Specify high-efficacy lamps for at least 90% of all lighting fixtures, N1104.1. Update the lighting note.

OUTDOOR LIGHTING CODE

Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
11/09/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-RES-1023-09073
1653 E BLACKLIDGE DR Zoning:R-2
Remodel

TRANSMITTAL DATE:‎November 9, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: As you are proposing two kitchen, Zoning will consider this a second unit and Impact fee will need to be accessed, Provide a breakdown showing square footage of each unit so that impact fees can be calculated correctly. If second kitchen is to be removed clarify on the next submittal.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov