Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-1023-09056
Parcel: 116141290

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1023-09056
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2023 Site Engineering NOT REQUIRED
11/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/13/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1023-09056 (450 N AVENIDA CARINA TUCSON, AZ 85745)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Update the OCPDs in the dedicated load center on sheet PV-4*. Show a new 20A OCPD and the Existing OCPD should be 30A (SE5000H-US max current: 21A * 1.25 = 26.25A). Reference NEC 690.8(A)(3) and 690.9(B)(1).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/26/2023 PDSD Application Completeness Express REVIEW COMPLETED