Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/13/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1023-09049 (4062 E GLENN ST TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Provide complete wire size calculations for both the new and existing systems. Total IQ8Plus-72-2-US micro inverters is 36 (new and existing). Reference NEC 690.8(A)(3) and (B)(1).
2. Provide a DG disconnect rated for the given currents and system size.
3. Provide Main Service Panel (MSP) taps in compliance with NEC 705.12(B)(2)(3) b Busbars.) 120% bus bar rule.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov