Permit Number: TC-RES-1023-09047
Parcel: 128111440

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-1023-09047
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2023 Site Engineering NOT REQUIRED
11/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/07/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC).
1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability for 115 MPH, or provide an engineer’s calculation, and sealed design, R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems
2. #8 AWG wire needs to be uprated to #6 AWG as marked on line drawing. Maximum conductor ampacity is determined by applying correction and adjustment factors for temperature of insulation rating of 90C and CCC (Current Carrying Conductor) proximity. Reference NEC 310.15, Table 310.15(B)(2)(a), 310.15(B)(2)(b) and 310.15(B)(3)(a). The adjusted conductor rating may not be less than the calculated Conductor Sizing. The OCPD rating shall not exceed the allowable ampacity of conductor, E3705.5.
Building_official@tucsonaz.gov
10/26/2023 PDSD Application Completeness Express REVIEW COMPLETED