Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/03/2023 | Site Engineering | APPROVED | |||
11/09/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/09/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1023-09043 (126 N STEWART AV TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. Provide Main Service Panel (MSP) taps in compliance with NEC 705.12(B)(2)(3) b Busbars.) 120% bus bar rule. Plans show a total design backfeed of 52.50A which is greater than the max allowed of 50A. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
10/25/2023 | PDSD Application Completeness | REVIEW COMPLETED |