Permit Number: TC-RES-1023-09010
Parcel: 126133130

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-1023-09010
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2023 Site Zoning APPROVED
11/14/2023 Site Engineering NOT REQUIRED
11/16/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/16/2023 Residential Building REQUIRES RESUBMIT TC-RES-1023-09010
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes.

SITE PLAN:

1. Show the distance between the building and property lines, R106.1.1.
2. The roof structure may not extend to a point closer than 3 feet from the neighboring property line without fire rated protection for fire spread. Provide compliance with R302.1 (City of Tucson Amended) by providing a clear 3 foot space to the property line or include a complete wall barrier with not less than one-hour fire-resistive construction in compliance with IBC Table 721.1(2).

SECTIONS - DETAILS:

1 Show a complete cross-section detail with post to foundation fasteners, R407.3 & R507.4.1.
2 Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.
3 Identify all fasteners for wind loading compliance. Show roof (uplift resistance) fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
11/01/2023 PDSD Application Completeness Express REVIEW COMPLETED This permit is being intaken for 4535 E MONTECITO ST, customer will need to submit a separate permit for 4533 E MONTECITO ST.