Permit Number: TC-RES-1023-08995
Parcel: 136390250

Address:
4671 S CANNA LN

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1023-08995
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2023 Site Zoning APPROVED
10/31/2023 Site Engineering NOT REQUIRED
11/09/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/09/2023 Residential Building REQUIRES RESUBMIT TC-RES-1023-08995
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes.

Provide a clear and concise construction plan set. Sample drawings for a wooden Carport are similar to the Porch Sample. Sample plans are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

STRUCTURAL PLANS:

1. Show a beam size with appropriate load carrying capacity (4x8 is undersized), R301.1 or provide an engineer’s calculation, design, and seal for a performance design when minimum sizes are not code compliant with the IRC, R301.1.

SECTIONS - DETAILS:

1 Specify method of transferring lateral forces from the roof diaphragm to the supporting structural elements (without fascia end-grain nailing), R801.2. Correct the 2x8 fascia connection shown at the elevation view on sheet 4.
2 Provide an engineer’s seal for detail #3 which is a performance design.

ELECTRICAL PLANS:

1. Show any electrical alterations.
2. The overhead service conductor over the proposed building requires an 8’ clearance above the roof, E3604.2.1. Check with TEP customer service for service line options. https://www.tep.com/electric-service-requirements

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
10/24/2023 PDSD Application Completeness Express REVIEW COMPLETED