Permit Number: TC-RES-1023-08963
Parcel: 136030220

Address:
8561 E 23RD ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-1023-08963
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2023 Site Zoning APPROVED
12/04/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/04/2023 Residential Building REQUIRES RESUBMIT Permit Review TC-RES-1023-08963 (8561 E 23RD ST TUCSON, AZ 85710)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/garage_sample.pdf

Unaddressed Items:
STRUCTURAL PLANS:

1. Provide a Roof Framing Plan showing the location and size of beams, headers, and rafters for supporting live and dead structural loads, R804. Identify live and dead loads.
2. Identify all fasteners for wind loading compliance. Show roof (uplift resistance) fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.
3. Show braced wall panel compliance for narrow framed walls with a garage door opening, Table R602.10.5. For prescriptive braced wall structures show a portal frame with hold-downs PFH method, Figure R602.10.6.2, or a portal frame at garage door PFG method, Figure R602.10.6.3, or a continuously sheathed portal frame CS-PF method, Figure R602.10.6.4.


SECTIONS - DETAILS:

4. Show the wall assembly with a 2” clearance above an exterior concrete surface, R317.1 item 5. The framed wall may require a concrete stem for achieving the 2” clearance between framing and concrete (R317.1 item 5).
5. Identify all fasteners for wind loading compliance. Show roof (uplift resistance) fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.

Electrical Plans:
6. Provide an electrical plan showing a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage, E3703.5. A 20 AMP receptacle outlet is required at each vehicle bay not more than 5.5 feet above the floor, E3901.9.
7. Notate the requirement for a carbon monoxide detector installation outside of bedroom doors, R315.3. This is required as permitted work is done within existing dwellings having attached garages or having fuel-fired appliances.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
11/17/2023 PDSD Application Completeness Express REVIEW COMPLETED