Permit Number: TC-RES-1023-08963
Parcel: 136030220

Address:
8561 E 23RD ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.4

Permit Number - TC-RES-1023-08963
Review Name: RESIDENTIAL NEW DWELLING v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2024 Site Zoning APPROVED
01/10/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/10/2024 Residential Building REQUIRES RESUBMIT Permit Review TC-RES-1023-08963 (8561 E 23RD ST TUCSON, AZ 85710)
3rd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/garage_sample.pdf

>>> The following comments were not addressed.

SECTIONS - DETAILS:

1. Show the wall assembly with a 2” clearance above an exterior concrete surface, R317.1 item The framed wall may require a concrete stem for achieving the 2” clearance between framing and concrete (R317.1 item 5). >>> The framed wall cannot be at ground level; it must be raised per the referenced code.

2. Show the door from a garage to dwelling with a 20-minute fire rating (or 1-3/8” solid core) with self-closing and self-latching provision, R302.5.1.

Electrical Plans:
3. Provide an electrical plan showing a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage, E3703.5. A 20 AMP receptacle outlet is required at each vehicle bay not more than 5.5 feet above the floor, E3901.9. >>> The receptacle in the storage room does not meet the referenced code.

4. Notate the requirement for a carbon monoxide detector installation outside of bedroom doors, R315.3. This is required as permitted work is done within existing dwellings having attached garages or having fuel-fired appliances.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/02/2024 PDSD Application Completeness Express REVIEW COMPLETED