Permit Number: TC-RES-1023-08896
Parcel: 11604072A

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-1023-08896
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2024 Site Zoning APPROVED
05/13/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/30/2024 Residential Building REQUIRES RESUBMIT TC-RES-1023-08896

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

SECTIONS - DETAILS:

1. Show the weep screed with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1. Update keynote #13 on a2.11 and a5.1.
2. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5. Update the Storage Room Section on a2.11.
3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF. Update the Storage Room Section on a2.11 and Addition Section on a5.1.

ELECTRICAL PLANS:

1. Interior alterations require the installation of smoke alarms in existing bedrooms, R314.2.2. Provide notation if the smoke alarms are existing or proposed.


If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
----------------------
04/16/2024 PDSD Application Completeness Express REVIEW COMPLETED