Permit Number: TC-RES-1023-08833
Parcel: 141167290

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1023-08833
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2023 Site Zoning APPROVED
10/27/2023 Site Engineering NOT REQUIRED
11/02/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/02/2023 Residential Building REQUIRES RESUBMIT TC-RES-1023-08833
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

SITE PLAN:

Provide a site plan showing the location of the electrical service panel.

FLOOR PLAN:

Provide a floor plan showing each proposed room with labeled function. Include the identification of adjacent rooms with door or window openings in the proposed space. Any existing altered bedrooms must show code compliance for egress, R310.

SECTIONS - DETAILS:

1. Clarify the exterior sheathing, R106.1. Sheet A1 & A2 shows T-111 but detail #3 on sheet S shows OSB with stucco covering. T-111 requires a ½” thickness since it is not a structural panel as 3/8” OSB or plywood.
2. Show a continuous #4 rebar reinforced footing at all exterior walls on sheet S, R403.1. Existing porch slabs may not include a complete foundation. Also, the exterior slab probably has a slope that could be leveled for providing the required 6” clearance above grade.
3. Clarify the placement of insulation with values for both walls and ceiling, R106.1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF.

MECHANICAL PLANS:

1. Show heating/cooling facilities in all habitable rooms, R303.9.

ELECTRICAL PLANS:

1. Smoke alarms are required in each bedroom and outside the doorway in the immediate vicinity, R314.3.
2. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
3. Show at least one wall-switch-controlled lighting outlet providing illumination on the exterior side of each egress door having grade level access R3903.3.
4. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16.

OUTDOOR LIGHTING CODE

Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
10/17/2023 PDSD Application Completeness Express REVIEW COMPLETED