Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-1023-08823
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/16/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1023-08823 (3546 E 27TH ST TUCSON, AZ 85713) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. Provide an electrical riser diagram, E3403. Notate the grounding and bonding method, E3603.4, E3607. Metallic gas lines must be bonded and not be used as the primary grounding method, E3608. 2. Show the mast height on the electrical riser diagram, NEC 230.24. a. Providing 8’ clearance above the porch roof Or relocate the service entrance to a code compliant location, E3604.2.1. The overhead service conductor over the proposed building requires an 8’ clearance above the roof, E3604.2.1. The necessary mast height at the existing panel location may not be a feasible installation. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||