Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-1023-08614
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/09/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-1023-08614 (4241 E LINDEN ST TUCSON, AZ 85712) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. Notate the circuit breaker size and conductor sizes and type being used, E3402.3, E3403. 2. Show weatherproof covers at electrical boxes in damp or wet locations, E3905.11. 3. Show or notate, all outdoor receptacles as GFCI protected, E3902.3. |
||
| 10/06/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |