Permit Review Detail
Review Status: Requires Resubmit
Review Details: ELECTRICAL RECONNECT v.1
Permit Number - TC-RES-1023-08583
Review Name: ELECTRICAL RECONNECT v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2023 | PDSD Application Completeness Express | VOID | Temporary power on its own is not permittable and the permit will need to be voided. All repairs due to fire damage must be addressed to its entirety and a temporary power inspection can be added under the approved/issued building permit. Just be sure you include Temporary power is needed in the description details when addressing ALL other building repairs. The property/parcel has multiple addresses and any property with more then 2 addresses/units is considered to be commercial. A Commercial addition/alteration permit type addressing all building repairs and complete set of plans is required. Please remember this is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. To learn more about the regulations and the process please visit our website for a whole list of material examples: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Commercial-Permits For questions:Yaritza.Leon@tucsonaz.gov520-837-4899 |