Permit Number: TC-RES-1023-08569
Parcel: 121113360

Address:
4807 E MABEL ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1023-08569
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/05/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1023-08569 (4807 E MABEL ST TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. The description of work is not clear enough for review. Please clarify if you need to have an inspection for SW gas to turn the meter on, or if work was done to fix a leak or other issue. If work was done on the gas pipe system, you will need to submit a gas template for review.

>>> IF no new work has been done, this doesn’t apply.
1. https://www.tucsonaz.gov/files/pdsd/permits/Gas_Piping_Template.pdf
See also: https://www.tucsonaz.gov/files/pdsd/permits/GAS_HANDOUT_2018_IRC_2019.2.4.pdf https://www.tucsonaz.gov/files/pdsd/permits/Sample_Gas_Template_0.pdf
Provide a gas piping plan showing the connection from the meter to the all gas fired appliances. Include pipe size, type and length. G2413.4.1.
2. Size the pipe based on the length from the meter to the farthest attached appliance and max demand of each branch using Table G2413.4(1) (Metallic Pipe). Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov