Permit Number: TC-RES-1023-08526
Parcel: 108201490

Address:
881 E MEADOW LN

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.2

Permit Number - TC-RES-1023-08526
Review Name: RESIDENTIAL SOLAR v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/01/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/01/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1023-08526 (881 E MEADOW LN TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. The EOR’s seal must be placed back on the updated plans for the structural sheets, R106.1.
Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
2. The #8 awg CU conductor, for tag 5, is undersized for the given 60A OCPD in the ConnectDER. Conductors shall be protected with OCPD’s having a rating not exceeding the allowable ampacity of the conductor, IRC E3705.5, reference NEC 240.21.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov