PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

Each dwelling unit with kitchen requires a separate Pima County assigned street address after Zoning approval, R319. https://www.pima.gov/1010/Addressing-Frequently-Asked-Questions

An impact fee payment is required for an ADU at the time of permit payment.

PLANS:

1. Provide the dimensions for the primary dwelling Covered Patio on sheet A2.1.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Clarify detail #4/A5.0 keynote #6 showing the air-impermeable rigid insulation material adhered to either side of the roof sheathing when the batt insulation option is installed.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe for supporting the existing and proposed dwellings and show an appropriate water meter size.
2. Clarify the Gas Piping Capacity Tables total developed length with Table G2413.4(1) on sheet P2.0. The capacities shown are for a 100’ length rather than 150’.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Show the minimum airflow rate setting and location of the device requiring this adjustable setting. A two or three bedroom dwelling under 1501 SF requires a 45 CFM continuous setting.

ELECTRICAL PLANS:

1. TEP may require the service panel for the property at the closest building to the service transformer. A service line change or a new meter location must be coordinated with TEP for approval. Show an underground feeder from a metered service panel to the more distant dwelling.
2. Update the Riser Diagram if relocating the meter panel, NEC 225.30 and E3403.
3. Show locations of each smoke alarm, R314 and a carbon monoxide detector, R315.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd