Permit Number: TC-RES-1023-08474
Parcel: 137335330

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1023-08474
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/03/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-1023-08474 (1732 W GREENLEAF DR TUCSON, AZ 85746)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. The #3 AWG AL conductor from the generator is undersized for the given 100A OCPD. The OCPD rating shall not exceed the allowable ampacity of conductor, E3705.5.
2. The spec sheet for the 18kw generator calls for an 80A OCPD. Show an 80A breaker at the generator per the spec sheet or show the allowable use of the 100A breaker, R102.4, R106.1.2. If an 80A OCPD is used, then the #3 AWG AL conductor can be used per NEC 240.4(B).
3. Remove the 20/22/24 kw spec-sheets from the submittal files.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/03/2023 PDSD Application Completeness Express REVIEW COMPLETED