Permit Number: TC-RES-1022-00225
Parcel: 133440580

Address:
9748 E 1ST ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1022-00225
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2022 Site Zoning APPROVED
11/21/2022 NPPO NOT REQUIRED
11/15/2022 Site Engineering NOT REQUIRED
11/21/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/15/2022 Residential Building REQUIRES RESUBMIT TC-RES-1022-00225
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Indicate the location and size of buildings, utility meters and lines supporting the alteration, R106.1.1. Show the electrical service panel location.

FLOOR PLANS:

1 Show any openings between garage and dwelling. A door from a garage to dwelling with a 20-minute fire rating (or 1-3/8” solid core) with self-closing and self-latching provision, R302.5.1.

SECTIONS - DETAILS:

1 Clarify the footing detail of the new exterior wall, R106.1.1. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.

ELECTRICAL PLANS:

1. Garage Branch Circuit: a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage, E3703.5.
2. Garage Receptacle Location: an outlet is required at each vehicle bay not more than 5.5 feet above the floor, E3901.9.
3. Show any lighting and switches, R3903.3.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review
11/04/2022 PDSD Application Completeness Express REVIEW COMPLETED