Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-0926-05400
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/29/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/29/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact PDSD-Permits@tucsonaz.gov Please resubmit addressing the following comment: 1)The Eaton service entrance barrier kit does not comply with the requirement in E3606.5 or 230.67. Please provide the spec sheet of the SPD to be install that is compliant, SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67 |
||
| 09/29/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |