Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0926-05400
Parcel: 130181710

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0926-05400
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/29/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact PDSD-Permits@tucsonaz.gov

Please resubmit addressing the following comment:
1)The Eaton service entrance barrier kit does not comply with the requirement in E3606.5 or 230.67. Please provide the spec sheet of the SPD to be install that is compliant, SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67
09/29/2026 PDSD Application Completeness Express REVIEW COMPLETED