| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/25/2026 | Residential Zoning | APPROVED | |||
| 10/02/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/02/2026 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit a comment response letter and corrected plan set addressing the following comments: 1) Please resubmit a plan set for the new scope of work, this is a duplicate plan set for the project submitted under T15CM01436 2) Demonstrate adherence to 690.12. Any modifications to the existing PV system including PV module relocation or must adhere to most currently adopted codes. 3) Series wiring for the modules exceed the 600V max V for residential projects. 690.7(A). Maximum voltage uses open-circuit rating voltage per 690.7(A)(1) |
||