Please resubmit addressing the following comments:
1) Include unit number on plan
2) Submit a Change of Address Request to include unit number to permit application
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/sub-records_071425.pdf
09/23/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact PDSD-Permits@tucsonaz.gov

Please resubmit addressing the following comments:
1)A Surge Protection Device (SPD) must be identified on the plans. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that it is UL-listed and code-compliant with E606.5, NEC 230.67, and/or by providing the model number of the Surge Protection Device (SPD) to be installed.
The SPD must have a nominal discharge current rating of not less than 10 kA, be UL 1449 listed, and be Type 1 or Type 2, in accordance with NEC 230.67.