Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0926-05258
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2026 Residential Engineering APPROVED
10/01/2026 Residential Zoning APPROVED
10/05/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/28/2026 Residential Building REQUIRES RESUBMIT TC-RES-0926-05258
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2024 IRC with amendments and building ordinances for all dwellings.

Provide a separate response letter addressing each comment with location of change on the plans.

PLANS:

1. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1.
2. Individual dwelling units require separation with a 1-hour fire-resistance rated assembly without openings, R302.3, in compliance with 703.3 of the 2018 IBC. Add “Type X” to detail #3/A3.1.
3. Provide a minimum 6 mil polyethylene vapor retarder with joints lapped not less than 6 inches between the concrete floor slab and the base course or the prepared subgrade where a base course does not exist, R506.3.3.

MECHANICAL PLANS:

1. Provide demand calculations in accordance with Manual J standards, M1401.3, M1601.1.
2. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Identify the device model number providing an adjustable setting and note the minimum continuous setting. A one-bedroom dwelling under 1501 SF requires a 30 CFM continuous setting.
3. Provide makeup air of not less than 100 square inches where a clothes dryer is placed in a closet, M1502.6.1.

ELECTRICAL PLANS:

1. Show a surge-protective device (SPD) as an integral part of or placed immediately adjacent to the service equipment, E3606.5.
2. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets, E3703.2 and E3901.3. Add a circuit along with #17.
3. Provide GFCI protection for appliance receptacle outlets, E3902.12 & 14. Include the Dishwasher, Electric range, Clothes dryer, Microwave oven and HVAC equipment.
4. Include the smoke detectors with combination type arc-fault circuit interrupters, E3902.20.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place inside near an indoor furnace or utility room, IECC R401.3. Add notation to plans.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
09/29/2026 Design Review - Standard REVIEW COMPLETED No significant impact from right-of-way, design review is not required for this project as presented.
09/25/2026 PDSD Application Completeness Express REVIEW COMPLETED