Permit Number: TC-RES-0926-05247
Parcel: 116240620

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0926-05247
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/22/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comment:
1) The SPD provided Eaton BRPSURGE has a 3 kA nominal discharge rating, this device does not comply with the requirement in E3606.5 or 230.67 nor match PV4 nor PV5 equipment description. Please provide the spec sheet of the SPD to be install that is compliant, SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67
09/21/2026 PDSD Application Completeness Express REVIEW COMPLETED