Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0926-05237
Parcel: 131043680

Address:
4809 E 28TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0926-05237
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/18/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact PDSD-Permits@tucsonaz.gov

Please resubmit addressing the following comments:
1)A Surge Protection Device (SPD) must be identified on the plans. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that it is UL-listed and code-compliant with E606.5, NEC 230.67, and/or by providing the model number of the Surge Protection Device (SPD) to be installed.
The SPD must have a nominal discharge current rating of not less than 10 kA, be UL 1449 listed, and be Type 1 or Type 2, in accordance with NEC 230.67.
09/18/2026 PDSD Application Completeness Express REVIEW COMPLETED Please submit the following: A signed Owner Builder Affidavit is required prior to issuance of permit. Submit a Owner Builder Affidavit. The Affidavit form is available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits , Owner must have a TDC Online account and be added to the permit as the contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf