Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0926-05219
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/18/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/18/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact PDSD-Permits@tucsonaz.gov Please resubmit addressing the following comments: 1) Include address to aerial view. Show the proposed location of the scope of work, this applies even if the location will remain the same. 2) A Surge Protection Device (SPD) must be identified on the plans. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that it is UL-listed and code-compliant with E606.5, NEC 230.67, and/or by providing the model number of the Surge Protection Device (SPD) to be installed. The SPD must have a nominal discharge current rating of not less than 10 kA, be UL 1449 listed, and be Type 1 or Type 2, in accordance with NEC 230.67. |
||
| 09/18/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |