Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0926-05082
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/14/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Provide a site plan showing where on the structure the minisplit will be installed 2) Equipment requiring service must be GFCI protected 210.8(E), E3902.13 3) Provide a 125-volt, 15- or 20-amp service receptacle within 25 feet of the condensing unit in accordance with NEC 210.63. 4) Provide HVAC equipment model numbers, capacities, and efficiency ratings for compliance verification 2024 IECC R403.7 5) Provide a Load Calc. for the electrical including additional load from the new unit. NEC 220 Part III. Include conductors and all supplemental equipment used to supply the new central unit. 6) Provide a Manual J calculation showing the sizing of the unit to be installed is adequate for the designated area. Additionally, provide the size of the existing HVAC unit. |
||
| 09/11/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |