09/14/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:
1) Provide a site plan showing where on the structure the minisplit will be installed
2) Equipment requiring service must be GFCI protected 210.8(E), E3902.13
3) Provide a 125-volt, 15- or 20-amp service receptacle within 25 feet of the condensing unit in accordance with NEC 210.63.
4) Provide HVAC equipment model numbers, capacities, and efficiency ratings for compliance verification 2024 IECC R403.7
5) Provide a Load Calc. for the electrical including additional load from the new unit. NEC 220 Part III. Include conductors and all supplemental equipment used to supply the new central unit.
6) Provide a Manual J calculation showing the sizing of the unit to be installed is adequate for the designated area. Additionally, provide the size of the existing HVAC unit.