Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-0926-04987
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/09/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Provide a comment response letter and address the following comments: 1) Provide load calculations including the EV charger (Standard or Optional are accepted). As of Jan. 1, the City of Tucson has adopted the 2024 I-codes and 2023 NEC. Verify that all calculations adhere to the variables present in the new code. EVSE to be calculated at a minimum of 7.2 kW or nameplate rating, whichever is greater. Conductors and OCPDs are to be sized as continuous loads (80% rule) 220.57 2) Provide a one-line diagram with all equipment to be installed. Show the number of conductors required for this installation and the conduit size to determine conduit fill does not exceed 40%. Include EGC and grounded conductors. 3) Show the location of the outlet is protected from vehicular impact, indicate return wall depth or show method that will protect the charger and associated electrical equipment E3404.10, 110.27(B) 4) EVSE outlet must be GFCI-capable, alternatively provide a means of GFCI protection (including GFCI Overcurrent Protection Devices (OCPD)) 625.54 5) Provide manufacturer specifications and wiring diagram for the proposed EVSE outlet to verify whether a grounded conductor (neutral) is required for the installation. Installation shall comply with NEC 110.3(B), 220.61, and 625.42. 6) Indicate the rating of the overcurrent protective device (OCPD or breaker) to be installed and include the equipment grounding conductor (EGC) size on the plans. Provide conductor sizing and overcurrent protection details sufficient to verify compliance with NEC 210.19, 240.4, and 250.122. |
||
| 09/09/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |