Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-0925-04766
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/01/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | PDSD Residential Review Section PROJECT: TC-RES-0925-04766 Gas Pipeline Replacement from furnace to roof-(2nd Review) (7009 S LUNDY DR) TRANSMITTAL DATE: October 1st, 2025 Comments: 1) The ¾” main line pipe is undersized for the given length (38ft) and total appliance demand (200,000BTU). Size the pipe based on the length from the meter to the farthest attached appliance and max total Branch demand of all attached appliances using Table G2413.4(1) (Metallic Pipe). Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1. 2) On the gas piping template, please update the template to indicate the length of pipe to all of the appliances. Please email any questions to: PDSD-Residential@tucsonaz.gov |
||
| 09/30/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |