Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0925-04745
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/17/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/17/2025 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | Please resubmit addressing the following: 1) The plans show existing PV is not demonstrated to be under PCS control. Provide documentation or system details verifying PCS control of all backfeed sources to ensure proper load management and busbar protection. 2) Clarify whether the POI breaker will be 110A or 125A, both electrical calc sheets show this number to be inconsistent (under AWG tables, within the legend). For any questions, please contact: PDSD-Residential@tucsonaz.gov |
||
| 09/29/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |