Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-RES-0925-04745
Parcel: 141096060

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0925-04745
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/17/2025 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT Please resubmit addressing the following:
1) The plans show existing PV is not demonstrated to be under PCS control. Provide documentation or system details verifying PCS control of all backfeed sources to ensure proper load management and busbar protection.
2) Clarify whether the POI breaker will be 110A or 125A, both electrical calc sheets show this number to be inconsistent (under AWG tables, within the legend).

For any questions, please contact: PDSD-Residential@tucsonaz.gov
09/29/2025 PDSD Application Completeness Express REVIEW COMPLETED