Permit Number: TC-RES-0925-04702
Parcel: 133050340

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0925-04702
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/14/2025 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT Please resubmit addressing the following comments:
1) The sum of supply sources (260A) exceeds the maximum allowable capacity (240A) for this 200A busbar. The main breaker rating plus all back fed breakers must not exceed 120% of the busbar rating per NEC 705.12(D)(2).
For any questions, please email: PDSD-Residential@tucsonaz.gov
09/24/2025 PDSD Application Completeness Express REVIEW COMPLETED