Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0925-04668
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/23/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/23/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | PDSD Residential Review Section PROJECT: TC-RES-0925-04668 Gas Line from meter to furnace, Range, Water Heater and Dryer-(1st Review) (3608 E MONTE VISTA DR) TRANSMITTAL DATE: September 23rd, 2025 Comments: 1) The 1” main line pipe is undersized for the given length (103') and total appliance demand (235,000 BTU) using Table G2413.4(1) (Metallic Pipe). Note: The length is measured from the meter to the furthest attached appliance for all sizing per G2413.4.1. Please resubmit a revised gas template showing an adequate pipe size from the meter to the farthest appliance. |
||
| 09/23/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |