Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL ADU REVISION v.2
Permit Number - TC-RES-0925-04639
Review Name: RESIDENTIAL ADU REVISION v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/21/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/21/2026 | Residential Building | REQUIRES RESUBMIT | As stated in previous comments, the 1hr fire rating is for the entire assembly in accordance with ASTM E119. The product you are proposing has not been approved or rated for use in lieu of a 1-hour rated assembly. In addition, per the approved plans, the separating floor is to be constructed per UL design FC 5410. The manufacturer’s materials state that the proposed product was tested for 2x10 equivalence as part of IRC R302.13 Exception 4. R302.13 applies to floor assemblies that are NOT required to be fire-resistance rated. The floor/ceiling assembly you are proposing to use this on is not covered under this section of the IRC. You may use this product IN ADDITION to the standard 1 hour rated assembly. Per your comment response letter, if you wish to use this product as part of a 120 min fire rated wall assembly per U349 please provide a revised wall detail showing conformance with Table 3 of manufacturer’s fire-resistance assembly requirements (included in the link below), to include the use of 5/16” cement fiber siding panels and two layers of 5/8” type X GWB. This product may be used only in addition to a standard approved fire rated assembly, not as a replacement. (https://noburn.com/wp-content/uploads/2023/02/TER-2010-01.pdf) |
||
| 08/10/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |