Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL ADU REVISION v.1
Permit Number - TC-RES-0925-04639
Review Name: RESIDENTIAL ADU REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/24/2026 | Residential Building | REQUIRES RESUBMIT | Per IRC R302.1 a 1 hour fire rated wall must be tested in accordance with ASTM E119 (or UL263) which covers full fire rated assemblies, not ASTM E-84. The proposed product is not UL listed for 263 and does not qualify as a substitute for a 1 hour fire rated wall assembly. | ||
| 07/22/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |