Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0925-04631
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/28/2025 | Site Zoning - Standard | NOT REQUIRED | |||
| 10/28/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/09/2025 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | Please resubmit addressing the following comments: 1) The sum of supply sources exceeds the maximum allowable capacity for this 100A busbar. The main breaker rating plus all backfed breakers must not exceed 120% of the busbar rating per NEC 705.12(D)(2) For any questions, please contact: PDSD-Residential@tucsonaz.gov |
||
| 09/19/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |