Permit Number: TC-RES-0925-04609
Parcel: 132102930

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-0925-04609
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2025 Residential Engineering NOT REQUIRED
10/22/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/13/2025 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0925-04609
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes.

Provide a response letter on separate file when submitting the updated construction plan set.

Structures built without a permit may require alteration for building code compliance. Compliant construction plans are required before a permit can be issued for the inspection.

STRUCTURAL PLANS:

1. Provide a Roof Framing Plan showing the beams sized for supporting live and dead structural loads (Table R602.7(3)) or provide an engineer’s calculation, design, and seal for a performance design when minimum sizes are not code compliant with the IRC, R301.1.

ELECTRICAL PLANS:

1. Show any electrical alterations.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
10/22/2025 Residential Zoning REQUIRES RESUBMIT FROM:
Georgia Pennington, Lead Planner
PDSD Zoning Review Section

PROJECT:
TC-RES-0925-04609
2001 E Jason Vista
Residential Addition/Alteration

TRANSMITTAL DATE: September 18, 2025

The site is in the R-1 zone (UDC 4.8-2). A “Single-Family Residence, Detached” is a permitted use in the R-1 zone, subject to use-specific standards 4.9.7.B.5-9.


1. (COMMENT) Draw, dimension, and label the front street half-right-of-way for E Jason Vista as 25'.

2. (COMMENT) In an R-1 zone, the minimum setback to an front property line is 20’. Only 1.64’ is shown.

A Design Development Option (DDO) application will be required to be submitted and approved before final Site Zoning approval can be provided for this permit.

For more information about the DDO process, including an application, see https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration#section-3

If you are interested in moving forward with the DDO to allow the reduced setback, upload the DDO application to the “Zoning Modifications/DDO” subrecord on this permit within TDC Online. For instructions on creating a subrecord, please see https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/sub-records.pdf

Once approval of the DDO is provided in a DDO Decision Letter, upload that letter and resubmit this permit following the two-week post-decision appeal period.

If you have any questions about this transmittal, contact Georgia Pennington at Georgia.Pennington@tucsonaz.gov .
09/18/2025 PDSD Application Completeness Express REVIEW COMPLETED