Permit Number: TC-RES-0925-04558
Parcel: 136203040

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-0925-04558
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2025 Residential Zoning APPROVED
10/14/2025 Residential Engineering NOT REQUIRED
10/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/07/2025 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0925-04558
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Facilitate a shorter back check time: provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance.

Provide a response letter on separate file with submitting the updated construction plan set.

Structures built without a permit may require alteration for building code compliance.

STRUCTURAL PLANS:

1. Provide a Roof Framing Plan showing the beams sized for supporting live and dead structural loads (Table R602.7(3)) or provide an engineer’s calculation, design, and seal for a performance design when minimum sizes are not code compliant with the IRC, R301.1. Replace the undersized 4x6 beam over the door opening.

SECTIONS - DETAILS:

1 Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5. Update detail #2/S2.0.

ELECTRICAL PLANS:

1. Garage Branch Circuit: a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage and detached garages with service, E3703.5. A receptacle is required at each vehicle bay not more than 5.5 feet above the floor, E3901.9. Additional receptacles are optional.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
09/16/2025 PDSD Application Completeness Express REVIEW COMPLETED