Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0925-04553
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/04/2025 | Residential Zoning | APPROVED | |||
| 11/04/2025 | Residential Engineering | NOT REQUIRED | |||
| 11/04/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/08/2025 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | Please resubmit addressing the following comments: 1) Provide a lag-bolt connection up-lift calculation and design, R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems 2) Provide a 3-line diagram identifying each component and circuit notating sizes. 3) OCPD for POI is oversized: AC Overcurrent Protective Device and Conductor Sizing for PV source Circuits and Module Interconnection Conductors (Imax x 1.25) Reference NEC 690.8(A)(3) and (B)(1). Show a complete calculation for determining OCPD and conductor requirements. (See also 706.21 for ESS) For any questions, please email: PDSD-Residential@tucsonaz.gov |
||
| 09/16/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |