Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: TC-RES-0925-04508
Parcel: 13212001T

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0925-04508
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/03/2025 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT Please resubmit addressing the following comments:
1) AC Overcurrent Protective Device and Conductor Sizing for PV source Circuits and Module Interconnection Conductors (Imax x 1.25) Reference NEC 690.8(A)(3) and (B)(1). Show a complete calculation for determining OCPD and conductor requirements. (See also 706.21 for ESS)
2) Provide Main Service Panel (MSP) taps in compliance with NEC 705.12; 705.12(B)(2)(3) b Busbars.) 120% bus bar rule.
3) Please indicate on the 3-line graph for how the PCS controls the entire PV system's production
09/12/2025 PDSD Application Completeness Express REVIEW COMPLETED