Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-0925-04439
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/17/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/17/2025 | Addressing Validation | REQUIRES RESUBMIT | Permits can only be for one address, this permit is for unit 1 only. A separate second permit will be required for the electric panel upgrade on unit 2. In addition, a change of address request will need to be applied for in the sub records of this permit to remove the unit 2 address from this permit. Once the address change request is completed on this permit, you will need to resubmit site plan showing proposed work only for 928 N Hoff Av Unit 1. Instructions for change of address can be found here: https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/sub-records.pdf Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions: Building_Official@tucsonaz.gov | ||
| 09/17/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | Please resubmit addressing the following comments: 1) Demonstrate compliance with NEC 230.2 (Number of Services). Each MSP must be permitted separately unless the panel has separate meters to differentiate between services. Please submit panel information if the service is going to be dual metered, otherwise submit one permit per MSP. For any questions, please email: Building_Official@tucsonaz.gov |
||
| 09/17/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |