Permit Number: TC-RES-0925-04419
Parcel: 138144100

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.2

Permit Number - TC-RES-0925-04419
Review Name: RESIDENTIAL ADD/ALT v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2025 Residential Building - Standard APPROVED Approved with redlines
11/04/2025 Residential Engineering APPROVED
11/06/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/06/2025 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL FROM: Zoning Review Section

PROJECT: TC-RES-0925-04419
533 W Santa Paula St. – R-1
Bathroom addition (2nd review)

TRANSMITTAL DATE: November 6, 2025

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 -.9.

1. This comment was not fully addressed. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Plot-Plan-Example, to include but not limited to:
a. Provide the owners name on the plot plan.
b. The provided lot coverage does not appear to be correct. Pedestrian sidewalks and concrete not used for vehicles are not included in the calculation.
c. Provide a dimension from the centerline of the street to the face of curb and from the face of curb to the property line. Per Construction Plan I-802, sheet 11, found at: https://maps-and-records.tucsonaz.gov/construction-plans/details/I-802, the distance from centerline of Santa Paula St. to the face of curb is 16’ and from the face of curb to the north property line is 9’.
d. Provide the legal description, “FIESTA PARK LOT 419” on the plot plan.
e. Provide the zoning of this parcel and all adjacent parcels on the plot plan.

2. The provided neighbor’s setback waiver does not meet the requirements. As stated before the waiver shall “the statement must be provided on the plot plan”. A setback waiver is required for the sheds shown along the east and west property line. All structures that are taller than 5’ and greater than 10’ square feet are required to meet perimeter yard setbacks.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
10/10/2025 Addressing Validation REVIEW COMPLETED
10/10/2025 PDSD Application Completeness Express REVIEW COMPLETED